Push enter to reset – Honeywell NXL User Manual

Page 67

Advertising
background image

 

 

 

 

Control Keypad

67(96)

7

53

Fieldbus fault

The data connection between the fieldbus
Master and the fieldbus board is broken

Check installation.
If installation is correct contact the
nearest Honeywell distributor

54

Slot fault

Defective option board or slot

Check board and slot.
Contact the nearest Honeywell
distributor

55

Actual value
supervision

Actual value has exceeded or fallen below
(depending on par. 2.7.22) the actual value
supervision limit (par. 2.7.23)

Table 7-4. Fault codes

7.4.6 Fault history menu (H5)

The Fault history menu can be entered from the Main menu by pushing the Menu button right when
the location indication H5 is visible on the keypad display.

All faults are stored in the Fault history menu in which you can browse through them using the
Browser buttons. You can return to the previous menu anytime by pushing the Menu button left.

The memory of the frequency converter can store a maximum of 5 faults in the order of appearance.
The latest fault carries the indication H5.1, the second latest H5.2 etc. If there are 5 uncleared faults
in the memory the next occurring fault will erase the oldest from the memory.

Pressing the Enter button for about 2 to 3 seconds resets the whole fault history.

Figure 7-9. Fault history menu

STOP

I/O term

READY

STOP

I/O term

READY

STOP

I/O term

READY

nxlk20.fh8

Push Enter to reset!