Control Keypad

77(96)

7


7.4.8 Modbus interface

NXL has a built-in Modbus RTU bus interface. The signal level of the interface is in accordance with
the RS-485 standard.


Protocol:

Modbus RTU

Baud rates:

300, 600, 1200, 2400, 4800,
9600, 19200, 38700, 57600 (bit/s)

Signal level:

RS-485 (TIA/EIA-485-A)

Input impedance:

2 kΩ


7.4.8.1

Modbus RTU protocol

Modbus RTU protocol is a simple but effective fieldbus protocol. Modbus network has a bus
topology, where every device has an individual address. With the help of the individual bus
addresses the commands are directed to the single devices within the network. Modbus supports
also broadcast -type messages, which are received by every device of the bus. Broadcast messages
are sent to the address ’0’ which is reserved for these messages.

The protocol includes CRC error detection and parity check for preventing the handling of messages
containing errors. In Modbus the data is transferred in hex mode asynchronically and a break of
approximately 3.5 characters is used as an end character. The length of the break depends on the
used baud rate.

Function
code

Function name

Address

Broadcast
messages

03

Read Holding Register

All ID numbers

No

04

Read Input Register

All ID numbers

No

06

Preset Single Register

All ID numbers

Yes

16

Preset Multiple Register

All ID numbers

Yes

Table 7-12. Modbus commands supported by NXL

RS-485 Transceiver

Control terminal

RS-485 A

RS-485 B

Terminal resistor 120Ω
X7 -> MF2-MF3
X9 -> MF4-MF6