Control keypad 79(96) – Honeywell NXL User Manual

Page 79

Advertising
background image

 

 

 

 

Control Keypad

79(96)

7

Status Word

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

-

-

-

-

-

-

-

-

F

Z

AREF

W

FLT

DIR

RUN RDY


Information about the status of the device and messages is indicated in the Status word. The Status
word
is composed of 16 bits the meanings of which are described in the table below:

Actual speed

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

MSB

LSB


This is actual speed of the frequency converter. The scaling is –10000...10000. In the application,
the value is scaled in percentage of the frequency area between set minimum and maximum
frequency.

Control word

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

-

-

-

-

-

-

-

-

-

-

-

-

-

RST

DIR

RUN


In Honeywell applications, the three first bits of the control word are used to control the frequency
converter. However, you can customise the content of the control word for your own applications
because the control word is sent to the frequency converter as such.

Speed reference

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

MSB

LSB


This is the Reference 1 to the frequency converter. Used normally as Speed reference. The allowed
scaling is –10000...10000. In the application, the value is scaled in percentage of the frequency area
between the set minimum and maximum frequencies.

Bit definitions

Description

Bit

Value = 0

Value = 1

RUN

Stop

Run

DIR

Clockwise

Counter clockwise

RST

Rising edge of this bit will reset active fault

RDY

Drive not ready

Drive ready

FLT

No fault

Fault active

W

No warning

Warning active

AREF

Ramping

Speed reference reached

Z

-

Drive is running at zero speed

F

-

Flux Ready