Honeywell NXL User Manual

Page 92

Advertising
background image

92(96)

Honeywell

Honeywell

Honeywell

Honeywell

10

10. DESCRIPTION OF EXPANDER BOARD NXLOPTAA


Description: I/O expander board with one relay output, one open collector output
and three digital inputs.

Allowed slots:

Honeywell NXL board slot E

Type ID:

16705

Terminals:

Two terminal blocks; Screw terminals (M2.6 and M3); No coding

Jumpers:

None

Board parameters:

None


I/O terminals on NXLOPTAA
Terminal

Parameter
setting

Description

X3

1

+24V

Control voltage output; voltage for switches etc, max. 150 mA

2

GND

Ground for controls, e.g. for +24 V and DO

3

DIN1

DIGIN:x.1

Digital input 1

4

DIN2

DIGIN:x.2

Digital input 2

5

DIN3

DIGIN:x.3

Digital input 3

6

DO1

DIOUT:x.1

Open collector output, 50mA/48V

X5

24 RO1/NC

DIOUT:x.2

25 RO1/C

26 RO1/NO

Relay output 1 (NO)
Switching capacity:

24VDC/8A

250VAC/8A

125VDC/0,4A

Table 10-1. I/O terminals of board NXLOPTAA


Note! The +24 V control voltage terminal can also be used to power the control module (but not the
power module).

Advertising