Vent clearances and framing, A. pipe clearances to combustibles, B. wall penetration framing – Heatiator GDST3831I User Manual

Page 31

Advertising
background image

31

Heatilator • GDST3831I • 2127-900 Rev. L • 3/13

A. Pipe Clearances to Combustibles

WARNING! Risk of Fire! Maintain air space clearance to
vent. DO NOT pack insulation or other combustibles:

• Between ceiling fi restops
• Between wall shield fi restops
• Around vent system

Failure to keep insulation or other material away from
vent pipe may cause overheating and fi re.

8

8

Vent Clearances and Framing

Figure 8.2 Wall Penetration

* Shows center of vent framing hole for top venting. The center of the hole is

one (1) inch (25.4 mm) above the center of the horizontal vent pipe.

B

A*

10 in.

10 in.

A*

B

38-7/8 in.

37-7/8 in.

Note: Heat shields MUST overlap by a minimum of 1-1/2 in. (38 mm).

SLP heat shield - designed to be used on a wall 4-3/8 in. to 7-5/8

in. (111 mm to 194 mm thick).

• If wall thickness is less than 4-3/8 the existing heat shields must be

field trimmed. If wall thickness is greater than 7-5/8 in. a DVP-
HSM-B will be required.

2-1/2 in. (64 mm)

top clearance at

wall shield firestops

1/2 in. (13 mm) bottom
clearance at wall
shield firestops

1 in. (25 mm)
clearance
bottom and sides

Heat

Shields

Wall

Shield

Firestop

WALL

3 in. (76 mm)

top clearance

1 in. (25 mm)
clearance around
vertical sections

Figure 6.1 Horizontal venting clearances to combustible

materials

B. Wall Penetration Framing

Combustible Wall Penetration

Whenever a combustible wall is penetrated, you must
frame a hole for the wall shield fi restop. The wall shield
fi restop maintains minimum clearances and prevents cold
air infi ltration.

• The opening must be framed on all four sides using the

same size framing materials as those used in the wall
construction.

• SLP pipe - A wall shield fi restop must be placed on each

side of an interior wall. A minimum 1-1/2 in. (38 mm)
overlap of attached heat shields must be maintained.

• See Section 10.L. for information for regarding the in-

stallation of a horizontal termination cap.

Non-Combustible Wall Penetration

If the hole being penetrated is surrounded by noncom-
bustible materials such as concrete, a hole with diameter
one in. greater than the pipe is acceptable.

Whenever a non-combustible wall is penetrated, the wall
shield fi restop is only required on one side and no heat
shield is necessary.

Advertising