H. installing vertical termination cap, I. installing decorative wall components – Heatiator GDST3831I User Manual

Page 39

Advertising
background image

39

Heatilator • GDST3831I • 2127-900 Rev. L • 3/13

SCREWS

CAULK

STORM
COLLAR

(1 of 3)

Figure 10.15

TERMINATION CAP

H. Installing Vertical Termination Cap

• Attach the vertical termination cap by sliding the inner

collar of the cap into the inner fl ue of the pipe section
while placing the outer collar of the cap over the outer
fl ue of the pipe section.

• Secure the cap by driving three self-tapping screws

(supplied) through the pilot holes in the outer collar of the
cap into the outer fl ue of the pipe (see Figure 10.15).

I. Installing Decorative Wall Components

A decorative wall thimble can be installed on wall through
which the vent passes. The decorative wall thimble is used
to cover the fi restop.

• Slide the decorative wall thimble over the last section of

horizontal pipe before connecting the termination cap to
the pipe.

• Once the pipe section and the termination cap have been

connected, slide the wall thimble up to the interior wall
surface and attach with screws provided. See Figure
10.16.

Figure 10.16 Wall Thimble

Important Notice: Heat shields may not be fi eld constructed.

J. Heat Shield Requirements for Horizontal

Termination

WARNING! Risk of Fire! To prevent overheating and fi re,
heat shields must extend through the entire wall thick-
ness.

DO NOT remove the heat shields attached to the

wall shield fi restop and the horizontal termination cap
(shown in Figure 10.17).

• Heat shields must overlap 1-1/2 in. (38 mm) mini-

mum.

There are two sections of the heat shield. One section
is factory-attached to the wall shield fi restop. The other
section is factory-attached to the cap. See Figure 10.17.

If the wall thickness does not allow the required 1-1/2 in.
(38 mm) heat shield overlap when installed, an extended
heat shield must be used.

• If the wall thickness is less than 4 in./102 mm (DVP)

or 4-3/8 in./ 111 mm (SLP), the heat shields on the cap
and wall shield fi restop must to be trimmed. A minimum
1-1/2 in. (38 mm) overlap MUST be maintained.

• Use an extended heat shield if the fi nished wall thickness

is greater than 7-1/4 in. (184 mm).

• The extended heat shield may need to be cut to length

maintaining suffi cient length for a 1-1/2 in. (38 mm)
overlap between heat shields.

• Attach the extended heat shield to either of the existing

heat shields using the screws supplied with the extended
heat shield. Refer to vent components diagrams in the
back of this manual.

• Rest the small leg on the extended heat shield on top

of the pipe section to properly space it from the pipe
section.