Position indication, Manual adjustment, Limitation of rotation stroke – Honeywell N20 User Manual

Page 4: Internal auxiliary switches, Override, Installation, Mounting instructions

Advertising
background image

N20, N34 SERIES MN7220, MN7234

63-2587—1

4

Voltage/Current Control Signal Selection Dip Switch

In its default shipping position, the voltage/current control

signal dip switch (see Fig. 4) is set to OFF (= voltage control).

as shown in Fig. 4. Setting it to ON results in current control.

Position Indication

The hub adapter indicates the rotation angle position by means

of the rotational angle scales (0...90° / 90...0°).

Fig. 6. Position indication

Manual Adjustment

IMPORTANT

In order to prevent equipment damage, you must

remove power before manual adjustment.

After removing power, the gear train can be disengaged using

the declutch button, permitting the actuator shaft to be

manually rotated to any position. The feedback signal will then

follow the new position.

Limitation of Rotation Stroke

Two mechanical end limits (adjustable in 3° increments) are

provided (20 Nm [175 lb-in] models, only) to limit the angle of

rotation as desired (see Fig. 7).

Fig. 7. Mechanical end limits

The mechanical end limits must be securely fastened in place

as shown in Fig. 8. Correct / incorrect tightening of end limits8.

Specifically, it is important that they properly mesh with the

rotational angle scales when the screws are tightened.

Fig. 8. Correct/incorrect tightening of end limits

Internal Auxiliary Switches

The internal auxiliary switches are set to change from

“common” to “normally open” at angles of 5° and 85°,

respectively, from the totally counterclockwise position.

Fig. 9. Internal auxiliary switches

Override

If terminal 3 of the terminal strip (see section “Wiring

Diagrams” on page 6) is unplugged, the stroke will be 0%;

reversing the rotation direction using the rotation direction

switch will result in a max. stroke of 100%. If terminal 3 is

jumped with terminal 1 (24 V), the stroke will be 50%.

INSTALLATION

These actuators are designed for single-point mounting.

IMPORTANT

In order to prevent equipment damage, you must

remove power or set the rotation direction switch to

the “Service/Off” position before manual operation.

Mounting Instructions

All information and steps are included in the Installation

Instructions supplied with the actuator.

90 90

60

30

60

30

0

0

10°

15°

92.5°

90°

-2.5°

85°

80°

75°

85°

80°

75°

-2.5°

90°

92.5°

10°

15°

10°

15°

90°

85°

80°

75°

CCW internal

auxiliary switch

CW internal

auxiliary switch

actuator scale: clockwise

auxiliary switch scale

actuator scale: counterclockwise

Advertising