Installation of fireplace – Heatiator Heatilator Wood Burning Fireplace SC60 User Manual

Page 21

Advertising
background image

21

7

Installation of Fireplace

CAUTION! Risk of Cuts/Abrasions. Wear protective

gloves and safety glasses during installation. Sheet metal

edges are sharp.

A. Things to Consider

• Location of chimney air kit (see Figure 7.4)

• Location(s) of outside air kit

• Electrical connections and/or wall switch

• Gas line piping

B. Position the Fireplace

• Place the fireplace on a continuous flat surface.

• Follow framing instructions in Section 6.

WARNING! Risk of Fire! Prevent contact with sag-

ging, loose insulation.

DO NOT install against vapor barriers or exposed

insulation.

• Secure insulation and vapor barriers.

• Provide minimum air space clearances at the sides

and back of the fireplace assembly as outlined in

Section 6.

Protective metal strips are placed 2 in. (51 mm) under the

front of the fireplace and must extend beyond the front

and sides of fireplace opening by 2 in. (51 mm).

1 in. (25 mm)

overlap

Figure 7.1 Position the Protective Metal Hearth Strips

C. Place Protective Metal Hearth Strips

WARNING! Risk of Fire! Protective metal hearth strips

MUST be installed.

DO NOT cover metal strips with com-

bustible materials. Sparks or embers may ignite flooring.

• Refer to Figures 7.1 and 7.2.

• Locate the two protective metal hearth strips measuring

approximately 26 in. x 4 in. (660 mm x 102 mm) included

with this fireplace.

• Slide each metal strip 2 in. (51 mm) under front edge of

fireplace.

• Overlap strips in the middle of fireplace opening by 1 in.

(25 mm) minimum..

• Metal strips must extend beyond the front and sides of

the fireplace opening by at least 2 in. (51 mm).

• Protect the front of a platform elevated above the hearth

extension with metal strips (not included with fireplace)

per Figure 7.2. See Section 11 for hearth extension

instructions.

D. Level Fireplace

• Level fireplace side-to-side and front-to-back.

• Shim with non-combustible material as necessary.

• Secure fireplace to framing with nailing flanges with a

minimum of two fasteners per nailing flange.

• Check fireplace opening for square to ensure proper fit

of glass doors. Measure diagonals of fireplace opening

to make sure they are equal.

Raised Platform

Floor

2 in.

(51 mm)

1 in. (25 mm) min.

overlap

2 in.

(51 mm)

Top piece must overlap

bottom piece

Figure 7.2 Protect the Front of an Elevated Platform

Heatilator • SC60 • 32838 • Rev AG • 7/12

Advertising