A. chimney requirements, Table 8.1 – Heatiator Heatilator Wood Burning Fireplace SC60 User Manual

Page 25

Advertising
background image

25

A. Chimney Requirements

Measure vertical distances from the base of the fireplace

as shown in Figure 8.2.

20 ft (6.10 m) max.

pipe between an

offset & return

Ceiling Firestop

35 ft (10.7 m)

max. straight

unsupported

chimney height

14.8 ft (4.51 m) min. height/single offset-return

20 ft. (6.10 m) min. height/double offset-return

90 ft (27.4 m) max. height

6 ft (1.83 m) max.

unsupported chimney

above roof

40 in.

(1016 mm)

Effective

Height

Figure 8.2 Chimney Requirements

Table 8.1

WARNING! Risk of Fire! You must maintain 2 in. (51

mm) air space clearance to insulation and other combus-

tible materials around the chimney system. Failure to do

so may cause overheating and fire.

Determine the chimney components needed to complete

your particular installation:
• Measure the total vertical height of the fireplace

installation from the base of the fireplace assembly to

the approximate location of the bottom of the termination

cap.

• Subtract the effective height of the fireplace assembly

(see Figure 8.2) from the total vertical height to determine

the overall height of the chimney installation.

• Create a schematic for your application similar to Figure

8.2 showing components required (referring to Table

8.1). Figure 8.1 identifies those components and where

used.

• Install a ceiling firestop whenever the chimney penetrates

a floor/ceiling.

NOTICE: A maximum of two pairs of offsets and returns

may be used.

CAUTION! Risk of Fire and/or Asphyxiation! DO

NOT connect this fireplace to a chimney flue servicing

another appliance.

DO NOT connect to any air distribu-

tion duct or system. These actions could cause over-

heating/fire in the chimney flue, or release of exhaust

fumes into the living areas.

• Minimum overall straight height

13.5 ft

4.11 m

• Minimum height with offset/return

14.8

4.51 m

• Maximum height

90 ft

27.43 m

• Maximum allowed shift between an offset and

return

4.2 ft

1.28 m

• Maximum chimney length between an offset/

return

20 ft

6.10 m

• Maximum distance between chimney

stabilizers

35 ft

10.67 m

• Double offset/return minimum height

20 ft

6.10 m

• Maximum unsupported chimney length

between offset and return

6 ft

1.83 m

• Maximum straight unsupported chimney height

above the fireplace

35 ft

10.67 m

• Maximum unsupported chimney above roof

6 ft

1.83 m

Heatilator • SC60 • 32838 • Rev AG • 7/12

HEIGHT OF CHIMNEY COMPONENTS

in.

mm

Chimney Stabilizer

SL3

4-3/4

121

Ceiling Firestops

FS338

0

0

FS339

0

0

FS340

0

0

Offsets/Returns

SL315

13-3/8

340

SL330

15-1/2

394

Roof Flashing

RF370

0

0

RF371

0

0

Chimney Sections*

SL306

4-3/4

121

SL312

10-3/4

273

SL318

16-3/4

425

SL324

22-3/4

578

SL336

34-3/4

883

SL348

46-3/4

1187

* Dimensions reflect effective height.