D. Install Termination Cap

Install the chimney sections up through the chase enclo-

sure.

Caulk the overlap seam of any exposed pipe sections

that are located above the roof line to prevent leaks

• Refer to termination cap instructions.

WARNING! Risk of Fire! The minimum overlap of cap

to pipe (as shown in the following illustrations) MUST

be met or chimney may separate from cap. Separation

allows sparks, heat and embers to escape.

NOTICE: Paint the termination cap with a rust-resistant

paint to protect against the effects of corrosion on those

parts exposed to the weather.

Heatilator • SC60 • 32838 • Rev AG • 7/12

Storm

Collar

Chimney

Pipe

Chase Top

Termination

Cap

Chase

6 in. (153 mm)

Minimum top of

chase to top of

chimney pipe

Collar

2 in. (51 mm)

Minimum Height

Do NOT

block air holes

Caulk gaps between

storm collar & pipe,

and storm collar

& chase top.

Termination cap pipe and chimney section must be snapped

together to maintain an overlap of 1-1/2 in. (38 mm).

Slip

storm collar

around chimney pipe

before termination

cap pipe is snapped

into the chimney

pipe.

Figure 9.4 Installing a TR344 Round Termination Cap

Storm

Collar

Chimney

Pipe

Chase Top

Termination

Cap

Chase

14 1/2 in. (368 mm)

Maximum

Collar

2 in. (51 mm)

Minimum Height

Caulk gaps between

storm collar & pipe,

and storm collar

& chase top.

Do NOT

block air

holes

3 clip brackets.

Slip over chase collar

and attach with screws

provided.

Termination cap pipe and chimney section must overlap 1-1/2 in. (38 mm)

Assemble

storm collar

around extended

termination cap

pipe

once cap is

installed.

Figure 9.5 Installing a TR342 Round Telescoping Termination

Cap

Chimney

Pipe

Chase Top

Termination Cap

Chase

Collar

2 in. (51 mm)

Minimum Height

Place waterproof

caulk or sealer under

each flange of the

termination cap and

on top of each screw

to help prevent leaks.

Flange

Termination cap pipe and chimney section must overlap 1-1/2 in. (38 mm)

2 in. (51 mm)

maximum

4 3/4 in. (121 mm)

maximum

The last section of pipe

must stop between 2 in. (51

mm) above the top of the

chase and 4 3/4 in. (121

mm) below the top of the

chase.

Figure 9.6 Installing an ST375 Square Termination Cap

TR344 Round Termination Cap

• ST375 Square Termination Cap