Programming Function Blocks and Features

Video Recorder – User Manual

108

Signal Select

Selects one of 48 inputs based on the action and outputs it as CVn OV.

Table 4-18 describes the Signal Select prompts. See Table 4-2 for additional prompts.

Table 4-18 Signal Select Prompts

Prompt

Range/Selections

Definition

OUTPUT LOW LIMIT

OUTPUT HIGH LIMIT

OFF or number

Displayed output value will be clamped and will flash when
these limits are exceeded.

INPUT #1 - INPUT #48

OFF, analog parameter,
number

Up to 48 input sources to be selected from according to the
ACTION.

ACTION

HIGH

Selects the highest value input.

LOW

Selects the lowest value input.

AVG

Averages the input values.

MIDDLE

Selects the middle (median) input value. If the number of
inputs is even, selects the sum of the middle two input values
divided by 2.

F-GOOD

(First Good) If inputs fail, selects the first good input to the
function block. For example, if inputs 1 and 2 fail, then input
3 is selected.

ANA-SW

(Analog Switch) Selects an input equal to the value of the
ANALOG SELECT parameter.

DIS-SW

(Discrete Switch) Selects Input #1 or #2 according to state of
DISCRETE SELECT.

ANALOG SELECT

OFF, analog parameter,
number

Example: if ASEL=3, then Input #3 is selected. If ANALOG
SELECT < 1, Input #1 is selected. The value of ANALOG
SELECT is truncated to a whole number. For example, if
ANALOG SELECT is 3.55, the value is truncated to 3 and
Input #3 is selected.

DISCRETE SELECT

OFF, discrete parameter,
0, 1

Selects Input #1 when DISCRETE SELECT is off (0); selects
Input #2 when DISCRETE SELECT is ON (1). Inputs 3-48
are unused.