Programming Function Blocks and Features

Video Recorder – User Manual

109

Compare

Compare can be used instead of an Alarm’s output to control a relay. It can also provide on/off control
with hysteresis.

Compares 2 inputs. Call the result of this comparison “Result”. Result is a pulse that goes ON(1) when
comparison is true, and OFF(0) when comparison is not true. If hysteresis is given a value, then Result
will not go OFF(0) until hysteresis value is exceeded. Result is then processed according to the
specified condition type and condition time. The final output is a discrete pulse CVn OS.

COMPARE

OPERATOR

&

HYSTERESIS

Input #1

Input #2

Result

CONDITION

TYPE

&

CONDITION

TIME

CVn OS

Figure 4-2 Compare Signal Flow

Table 4-19 and Table 4-20 describe the Compare prompts. See Table 4-2 for additional prompts.

Table 4-19 Compare Prompts

Prompt

Range/Selections

Definition

INPUT #1

INPUT #2

OFF, analog parameter,
number

Input sources to be compared.

OPERATOR

EQ, GT, LT, GTE, LTE, NEQ

The Result will be set to ON(1) when the comparison is true:

Input #1 OPERATOR Input #2

where OPERATOR is:

EQ(=), GT(>), LT(<), GTE (

), LTE (

), NEQ(

)

The Result will be set to OFF(0) when the comparison is false.

HYSTERESIS

Number, OFF

Applies to all operators except EQ and NEQ. If given a value,
hysteresis determines when Result goes OFF(0) after the
comparison becomes false.

Operator Hysteresis

Function

GT:

Result goes OFF when Input #2 - Input #1

Hyst

GTE:

Result goes OFF when Input #2 - Input #1 > Hyst

LT:

Result goes OFF when Input #1 - Input #2

Hyst

LTE:

Result goes OFF when Input #1 - Input #2 > Hyst

See Figure 4-3.

CONDITION TYPE

NONE, DELAY, EXTEND,
PULSE, RT PULSE

See Table 4-20.

CONDITION TIME

OFF or number

Enter number of seconds of condition time. See Table 4-20.