Programming Function Blocks and Features

Video Recorder – User Manual

125

Interval Timer

This timer counts down from the preset value in minutes. This time remaining is CVn OV. The timer
has a single discrete output CVn OS which is ON(1) while the timer is actively counting or while RESET
is ON(1), and OFF(0) while the timer has timed out to zero. When RESET/RUN switches ON(1) the
timer resets to the preset value; an ON(1) to OFF(0) transition starts the timer.

Table 4-34 describes the Interval Timer prompts. See Table 4-2 for additional prompts.

Table 4-34 Interval Timer Prompts

Prompt

Range/Selections

Definition

PRESET

OFF, analog parameter,
number

Timer counts to zero from this number of minutes.

RESET/RUN

OFF, discrete parameter, 0, 1

Controls the operation of the timer.

RANGE LOW

RANGE HIGH

OFF or number

Enter the output’s display limits. Output is not clamped or
flashed when it exceeds these limits.