Programming Function Blocks and Features

Video Recorder – User Manual

128

Mass Flow

By compensating for variations in fluid temperature and pressure, Mass Flow is used to obtain a more
precise fluid flow measurement from an orifice plate developing a differential pressure. The output CVn
OV is mass flow and is calculated from the following formula for U.S. Units Of Measurement:

MF = FACTOR 1 x SQRT [DP INPUT x (PRESSURE INPUT+14.7) / (TEMPERATURE INPUT + 459)]

where

FACTOR 1 is calculated by user

DP INPUT is differential pressure in inches of water

PRESSURE INPUT is in PSIG

TEMPERATURE INPUT is in °F

Or, Mass flow is calculated from the following formula for International Units Of Measurement:

MF = FACTOR 1 x .569 x SQRT [DP INPUT x (PRESSURE INPUT +101.4)/(TEMPERATURE INPUT + 273)]

where

FACTOR 1 is calculated by user

DP INPUT is differential pressure in KPASCALS

PRESSURE INPUT is in KPASCALS

TEMPERATURE INPUT is in °C

Table 4-37 describes the Mass Flow prompts. See Table 4-2 for additional prompts.

Table 4-37 Mass Flow Prompts

Prompt

Range/Selections

Definition

OUT LOW LIMIT

OUT HIGH LIMIT

OFF or number

Displayed output value will be clamped and will flash
when these limits are exceeded.

DP INPUT

OFF, analog parameter,
number

Differential pressure input

PRESSURE INPUT

OFF, analog parameter,
number

Pressure input in PSIG or KPASCALS

TEMP INPUT

OFF, analog parameter,
number

Temperature in °C or °F

UNITS OF MEASURE

US or International

Units of measure

FACTOR 1

OFF, analog parameter,
number

Flow factor for the particular installation