Programming Function Blocks and Features

Video Recorder – User Manual

147

4.16 Program Constants

Constants can be programmed here and their values edited Online. Select a constant to program.

Table 4-52 describes the Constant prompts. See Table 4-2 for additional prompts.

Table 4-52 Constant Prompts

Prompt

Range/Selections

Definition

VALUE OFF,

analog

parameter, number

If a number, the Constant may be altered Online from the Data
Entry menu. If a parameter, this parameter can be directed by
DESTINATION to override certain programmed values.

INPUT LOW LIMIT

INPUT HIGH LIMIT

OFF or number

Display limits (for when viewing Constant on trend display or on
bar displays).

DESTINATION

See Destination defined on next page.

NONE

No

destination

LPn GN LOOPn GAIN1

LPn PB LOOPn PROP. BAND #1

LPn RS LOOPn RESET #1

LPn RA LOOPn RATE #1

LPn RB

LOOPn RATIO BIAS

LPn IS LOOPn SP INC SLEW LIMIT

LPn DS LOOPn SP DEC SLEW LIMIT

LPn HS LOOPn SP HIGH LIMIT

LPn LS LOOPn SP LOW LIMIT

AOn IS AOn INC SLEW LIMIT

AOn DS AOn DEC SLEW LIMIT

AOn HS AOn IN HIGH LIMIT

AOn LS AOn IN LOW LIMIT

AOn IT AOn IMPULSE TIME (type DAT)

COMM CONSTANT

Yes/No

When enabled, any constant writes via modbus communication
will only be written to the RAM copy of the configuration and not
to the non volatile flash copy.

When the unit cold starts, the constant values set up to be
periodically written via communications will revert back to any
value that was manually set via the local HMI. The local HMI will
always write the constant value to the RAM and non volatile flash
which will be preserved across a power cycle.