4.24 Scan Rate

Scan rate is the time required to measure inputs, execute function blocks (AI, Loops, AO, DI, DO, CV,
etc.) and update outputs. It is also known as the machine cycle, scan cycle, and update rate.

The Scan Rate prompt lets you set the scan rate of the instrument to a value slower than the maximum
rate allowed by the hardware. The hardware will determine the default scan rate. Allowable entries are
250 milliseconds, 500 milliseconds, 1 second, 2 or 3 seconds. 250 ms rate is only available on 4 input
units.

We recommend the following scan rates for the following configurations.

Table 4-70 Suggested Scan Rates

Inputs

Scan Rate

W/Control

Up to 4

Up to 12

Up to 16

Up to 24

Up to 32

Up to 44

Up to 48

250 msec

500 msec

750 msec

1 sec

1.5 sec

2.0 sec

3.0 sec

500 msec

1 sec

1 sec

1.5 sec

2 sec

2 sec

3 sec

NOTE

These are suggested scan rates. In general, if your instrument responds too slowly, use a slower (higher)
scan rate. You can use a faster (lower) scan rate than suggested here, but be aware of possible sluggish
display and button response time.