Setpoint Profiler

Video Recorder – User Manual

178

5.2 Components of a profile

Two PVs available

Each profile can monitor up to 2 process variables. The second PV is for monitoring a second variable
related to your process. The value of each PV is compared with the value of the profile. If the
difference between either PV and the profile value exceeds specified amounts, the profiler will Hold
(soak), if enabled to do so.

Number of segments

Up to 63 segments may be in a profile.

Time Units

All segments use the same time base (seconds, minutes, or hours).

4 types of ramp segments

There are four ramp types selectable at the RAMP TYPE prompt.

1. Value/Duration

2. Time

3. Rate

4. External

Value/Duration (Val/Dur)Ramp Type

This is the only ramp type that allows consecutive ramps or soaks. VALUE is the beginning value of the
segment; TIME is the time needed to reach the VALUE of the next segment.

Segment #1
Time

Segment #2
Time

Segment #3
Time

Segment #4
Time

Segments #1 & #2

Valu e

Segment #3
Value

Segments #4 & #5

Value

Segment #5
Time

Time = time to reach next segment Value

Ramp Type = Value/Duration

Time = duration of soak
Value = value of soak

Value = beginning value of current segment

Features of this ramp type

* Allows consecutive ramps or soaks

* First segment can be a ramp or soak

Ramp segments

Soak segments

Figure 5-3 Value/Duration Ramp Type