Setpoint Profiler

Video Recorder – User Manual

179

To properly terminate a Val/Dur profile you must program the segment beyond the last segment with

the following:

1. The value you want the program to “end” with. Looking at Figure 5-3, the last segment is a soak,

thus the Value of segment #6 should be set to the same value used in segment #5. Any other value
will cause segment #5 to be a “ramp” since the value will ramp up (or down) from segment #5’s
value to segment #6’s value.

2. Set the TIME to “OFF”.

Time Ramp Type

Each ramp segment’s TIME is the time allotted for the profiler output to reach the next soak segment’s

VALUE. The ramp segment’s VALUE prompt is not used.

Soak segments

Segment #1
Time

Segment #2
Time

Segment #3
Time

Segment #1
Value

Segment #3
Value

Ramp Type = Time

Time = duration of soak
Value = value of soak

Features of this ramp type

* First and last segments must be soaks

* No consecutive ramps or soaks

Ramp segments

Value = not used in ramp segments

Time = time needed to reach next soak segment Value

Figure 5-4 Time Ramp Type