Setpoint Profiler

Video Recorder – User Manual

188

Parameter name

Definition

Triggered
by

Conditions
present

Result

SHUTDOWN

When Shutdown is activated by a discrete
input or by the operator menu, the profiler
jumps from the batch phase to the shutdown
phase of a multiphase profile. The shutdown
phase begins at the segment defined by the
parameter BATCH LAST SEGMENT+1.
Shutdown is useful when you need to shut
down your process without waiting for the
profiler to finish a batch.

Example

BATCH FIRST SEGMENT, which specifies the
start of the batch phase of the profile, is set at
Segment 3. The last segment of the batch
phase, BATCH LAST SEGMENT, is set at
Segment 7. The last segment of the profile is
Segment 9. When SHUTDOWN changes
from OFF to ON, the profiler will jump to
Segment 8, the first segment of the shutdown
phase of the profile.

See Figure 5-12 Shutdown

Rising
edge

Profiler is in
Run, Hold, or
End

Profiler
jumps to
BATCH
LAST
SEGMENT
+ 1

Batch Segments

Startup Segments

Shutdown Segments

BATCH FIRST SEGMENT

BATCH LAST SEGMENT

BATCH LAST SEGMENT + 1

END (batch)

END (shutdown)

Figure 5-12 Shutdown

RAMP
INCREMENT

See External Ramp Type on page 180.

Rising
edge

Profiler is in
Run mode &
RAMP TYPE
of profiler is
External

Profiler
increments
by amount
specified
by the
segment’s
TIME.

Advertising