Setpoint Profiler

Video Recorder – User Manual

189

Parameter name

Definition

Triggered
by

Conditions
present

Result

GUARANTEED
SOAK

See Guaranteed Soak on page 182.

Level ON

Excessive
deviation
between
profiler and
PV #1 or PV
#2 & the
segment’s
GUAR SOAK
#1 or GUAR
SOAK #2 is
enabled.

Profiler is
put on Hold

HOLD
LEVEL/EDGE

EDIT

Grants access to the profile’s segments
edition page, see table 5-5.

5.4 How to set up a profiler

Up to 4 profilers can be programmed, depending on the options on your instrument. There are two
menus for programming a profiler: PROGRAM PROFILERS in the Program menu, and SETPOINT
PROFILES in the Online menu. Both must be accessed to program a profiler. Both menus are
described in this section.

Program Profilers menu (in Program mode)

This menu lets you define various parameters for controlling the profiler’s execution. To access the
Program Profilers menu:

1. Press the Menu button until a main menu is displayed.

2. Select Set Mode and change the mode to Program.

3. Select Program Profilers.

4. Select a profiler (#1 through #4) to program. Only profilers that are not actively running are

selectable.

Table 5-3 briefly describes the prompts for all profilers. For detailed descriptions, refer to Sections 5.2
and 5.3. See Table 4-2 for additional prompts.