Setpoint Profiler

Video Recorder – User Manual

190

Table 5-3 Program Profiler Prompts

Prompt

Range/Selections

Definition

DISPLAY LO LIM

OFF or number

Enter the lower limit for the SP Trend
display. Allow for the maximum and
minimum Profiler and PV values.

DISPLAY HI LIM

OFF or number

Enter the upper limit for the SP Trend
display, allowing for the maximum and
minimum Profiler and PV values.

PV #1

OFF, analog parameter, number

Program the profiler to monitor a process
variable. PV #1 is trended on the SP
Trend display. PV #1 is compared to the
profiler’s value to determine deviation.
Excessive deviation between PV #1 and
profiler value can cause a Hold
(guaranteed soak).

PV #2

OFF, analog parameter, number

This is an optional PV that can also be
monitored and can be used to determine
deviation from profiler value. PV #2 is
shown on SP Trend display’s Point/Detail
menu. PV #2 is also trended on SP Trend
display.

START

Discrete parameter, 1, 0, or OFF

See Start on page 185.

RESET/RUN

Discrete parameter, 1, 0, or OFF

See Reset/Run on page 185.

HOLD

Discrete parameter, 1, 0, or OFF

See Hold on page 186.

ADVANCE

Discrete parameter, 1, 0, or OFF

See Advance on page 186.

HOT START

Discrete parameter, 1, 0, or OFF

See Hot Start on page 186.

FAST FORWARD

Discrete parameter, 1, 0, or OFF

See Fast Forward on page 187.

SHUTDOWN

Discrete parameter, 1, 0, or OFF

See Shutdown on page 188.

RAMP INCREMENT

Discrete parameter, 1, 0, or OFF

See External Ramp Type on page 180.

GUARANTEED SOAK

Discrete parameter, 1, 0, or OFF

See Guaranteed Soak on page 182.

HOLD LEVEL/EDGE

LEVEL or EDGE

Select LEVEL to Hold the profiler while
the Hold discrete is Level ON, and
resume Run when the Hold discrete is
Level OFF.

Select EDGE to Hold the profiler after the
Hold discrete changes from OFF to ON,
and resume Run after the Start discrete
changes from OFF to ON.