How to start a profiler

A profiler can be started from the Ready, Hold or End state.

Table 5-13 Profiler Starting Procedure

Step

Action

Result/Notes

1

Press Display button until the Setpoint Trend
is displayed.

SP1

PROFIL01

500.00

PV 0.00
SP 0.00

0.00

0:00:00

SEG1/9

READY

2

Press Tab button to display the profile menu.

SP1

500.00

PV 0.00
SP 0.00

0.00

0:00:00

SEG1/9

READY

START
HOLD
RESET
ADVANCE
SHUTDOWN
EVENTS
DETAIL
SUMMARY
EDIT
LOAD

PROFIL01

3

Cursor is on Start. Press Enter.

Profiler starts running at segment #1 if in Ready
or End or resumes running from its Hold state. If
in Ready state and Hot Start has been activated,
profiler will start at the first point in the profile
where the present value of PV #1 occurs. Event
outputs assume their states as of the beginning of
the running segment. Profiler status on lower
right of display indicates RUN after you start the
profiler.

ATTENTION

A profile can also be started by pressing the F1 button, but only if that profile’s START parameter was
configured as SY1 F1. See Section 5.4.