Pretune Abort messages

One of the following messages is displayed when an unusual event has aborted the pretune. “PTA”
means “Pretune Abort.”

Table 7-14 Pretune Abort Messages

Message

Meaning/User action required

PTA-WARM START

A warm start occurred during pretune. Repeat
pretune.

PTA-WENT OFFLINE

Instrument went out of Online mode during pretune.
Repeat pretune.

PTA-LOOP STATUS

Loop has PV that is bad (i.e. failed sensor)

OR

PV is a constant value such as from an upstream
block in manual

OR

Loop has back calculation value from a downstream
block that is bad or is the result of the downstream
block being in manual.

Repeat pretune.

PTA-AM SEL CHNGE

Loop switched between automatic and manual

modes. Repeat pretune.

PTA-SP SEL CHNGE

Loop was in automatic mode and an attempt was

made to switch between Setpoint #1 and Setpoint #2.
Repeat pretune.

PTA-OUT MOVED

Loop was in manual mode and loop’s output value
changed. Repeat pretune.

PTA-SP MOVED

Loop was in automatic mode and the setpoint value
changed. Repeat pretune.

PTA-LOOP OS

Loop is out of service. Fix loop before repeating
pretune.

PTA-LOOP NOT CFG

Loop is not configured. Configure loop before
repeating pretune.

PTA-BAD STEP SIZ

Step size is turned off. Set step size to a value
before repeating pretune. See Table 7-11.

PTA-ONOFF LOOP

Cannot pretune an on/off type loop.

PTA-BAD SN RATIO

Increase step size. See Table 7-11.

PTA-BAD OSC

Repeat pretune with smaller gain or proportional
band in loop.

PTA-BAD ID VALUE

Increase step size. See Table 7-11.

PTA-DB ACCESS

Unknown hardware problem. Consult service.

PTA-TASK FAIL

Unknown hardware problem. Consult service.