5 ao module calibration – Honeywell VRX180 User Manual

Page 260

Advertising
background image

Maintenance

Video Recorder – User Manual

246

Additional calibration selections allow you to perform other calibration procedures:

CALIBRATE REFERENCE JUNCTIONS – for calibrating the two Cold Junction (CJ) references on AI
module.

COPY ANALOG INPUT CALIBRATION – for copying calibration values from one AI module channel to
another.

RESET ANALOG INPUT CALIBRATION – to restore AI module channels to their factory calibration.

RESET REF. FUNCTION CALIBRATION – to restore CJ reference to their factory calibration values.

8.5 AO MODULE calibration

Two calibration selections are accessible under the CALIBRATE AO menu selection

CALIBRATE AO CHANNEL – to calibrate the zero offset and span values of the AO module channels to
user-defined values.

RESTORE AO FACTORY CAL – to restore factory calibrated to an AO module channel.

The AO module contains a wire jumper (labeled ST1) on the PWA. Cutting this jumper will prevent any
changes to initial calibration values of the module and prevent any further field calibration.
See Figure 8-1 for the location of the jumper.

S T 1

O U T 4

+

_

O U T 3

+

_

O U T 2

+

_

O U T 1

+

_

0-2

0m

A

!

C a va lier S T 1

M o du le d e s o rtie

an alog iq u e

Wire Jumper ST1

Analog Output

Module

Figure 8-1 AO Module Jumper ST1

Calibrate Analog Outputs

For CAT calibration, a precision milliammeter or a precision resistor and voltmeter is required.