Diagnostic and error messages

Video Recorder – User Manual

256

Table 9-4 Error Messages (continued)

Error

Description

User Action

Incorrect Input
coordinates

The Advanced Splitter CV was programmed with
input limits for Output#2 (A2) only, or for Output#1 &
#3 (A1 & A3) only, or for Output#3 (A3) only.

Re-program input limits for
Output#1 only, Outputs #1 & #2,
or Outputs #1, #2, & #3.

Incorrect Number of
Parameters for function

The function was not programmed with the minimum
number of parameters. for example, the Math CV
requires at least 2 inputs to function properly.

Program function with at least the
minimum number of parameters.

Incorrect Output
Coordinates

The Advanced Splitter CV was programmed with
output limits for Output#2 (A2) only, or for Output#1 &
#3 (A1 & A3) only, or for Output#3 (A3) only.

Re-program output limits for
Output#1 only, Outputs #1 & #2,
or Outputs #1, #2, & #3.

Invalid Algorithm Code

Bad algorithm code has been given, bad algorithm
choice. Probably caused by someone incorrectly
editing the configuration file or by a corrupt .LNC file.

Verify programming of affected
function block.

Invalid Block Number

Probably caused by someone incorrectly editing the
configuration file or by a corrupt .LNC file.

Verify programming of affected
function block.

Invalid Block Type

Probably caused by someone incorrectly editing the
configuration file or by a corrupt .LNC file.

Verify programming of affected
function block.

Invalid Channel in Point
spec

Invalid channel has been found.

Verify programming of affected
function block.

Invalid Equation

Free form math equation is invalid.

Check equation.

Invalid Function Block
Request

Probably caused by someone incorrectly editing the
configuration file or by a corrupt .LNC file.

Verify programming of affected
function block.

Invalid Index code

Probably caused by someone incorrectly editing the
configuration file or by a corrupt .LNC file.

Verify programming of affected
function block.

Invalid Input Connection

Function block is programmed with wrong input type.
Probably caused by someone incorrectly editing the
configuration file or by a corrupt .LNC file.

Verify programming of affected
function block.

Invalid Machine Update
Rate

Bad machine scan rate.

Re-enter machine scan rate.

Invalid Parameter Code

Bad parameter code has been found. Generally
caused by transferring configurations between
instruments with different software versions.

Verify programming of affected
function block.

Invalid Parameter for
Data Type

Probably caused by someone incorrectly editing the
configuration file or by a corrupt .LNC file.

Verify programming of affected
function block.

Invalid Tag

Probably caused by someone incorrectly editing the
configuration file or by a corrupt .LNC file.

Verify programming of affected
function block.

Invalid Tag Request

Probably caused by someone incorrectly editing the
configuration file or by a corrupt .LNC file.

Verify programming of affected
function block.

Invalid Type in Point
Spec

A class of block was detected that is invalid for the
product.

Verify programming of affected
function block.

Lag or Delay Less than
Zero

AI lag or delay is less than zero.

Change lag or delay to greater
than or equal to zero.