Diagnostic and error messages

Video Recorder – User Manual

258

Table 9-4 Error Messages (continued)

Error

Description

User Action

Trend Has Too Many
Points For Rate Selected

Data Storage cannot store more than 3 points at 1/4
second scan rate.

Change number of points to be
compatible with scan rate.

Type Does Not Exist

A function block type was loaded that does not exist.
For example, you loaded a Profile but the unit does
not have the Profile option.

Re-program or re-load correctly.

Type Incompatible With
Hardware

Analog output type is different from hardware setting.
Attempted to assign 6

th

relay as a DAT function.

Change programming to be
compatible with the hardware or
vice versa, then reload
configuration or reconfigure the
block.

Type Requires Hardware

Hardware is missing for the programmed analog
output or discrete output relay.

Either ignore the message
knowing that those particular
points did not get loaded or verify
configuration and make sure that
the points that are in the
configuration match the hardware
components.

Undefined Function Block
Request

Internal Error.

No user action.

Value Written to
Indirected Point

An input has been connected and user has tried to
write a value to that input. For example, if a control
loop setpoint is connected to AI1 OV, you will receive
this message if you try to change the loop setpoint
online.

Avoid changing connected values.

X Axis Must Increase

Appears if AI is custom type or CV is Function
Generator and if Xn > Xn+1.

Re-program Xn < Xn+1.

X Axis Not Increased
Enough

Appears if AI is custom type or CV is Function
Generator and if X does not increase by at least
0.00001.

Re-program X.

Y Axis Not Increased
Enough

Appears if AI is custom type or CV is Function
Generator and if Y does not change by at least
0.00001.

Re-program Y.