15 deg + 15 deg mounting angle limits – Honeywell VRX180 User Manual

Page 31

Advertising
background image

Installation

Video Recorder - User Manual

17

NOTE: When installing the video recorder, the following limits should be respected:

- 15 Deg

+ 15 Deg

Mounting angle limits

2.4 Wiring the video recorder

2.4.1 Recommendations

CAUTION

• All wiring must be in accordance with local electrical codes and should be carried out by authorized and

experienced personnel.

• The ground terminal must be connected before any other wiring (and disconnected last).
• A switch in the main supply is mandatory near the equipment.
• If an external fuse is used to protect the electrical circuit to the video recorder, the fuse should match the

video recorder fuse rating (fuse type) as well as for the fuseholder.

• Sensor wiring should be run as far as possible from power wiring. (motors, contactors, alarms, etc.)
• To reduce stray pick-up, we recommend the use of a twisted pair sensor wiring.

• EMI effects can be further reduced by the use of shielded cable sensor wiring. The shield must be

connected to the ground terminal.

Failure to comply with these instructions may result in product damage.