Programming and operating concepts and procedures – Honeywell VRX180 User Manual

Page 49

Advertising
background image

Programming and Operating Concepts

Video Recorder – User Manual

35

3. Programming and Operating Concepts and Procedures

3.1 Overview

This section explains the instrument’s programming and operating concepts and procedures. Read and
understand this section before attempting to program and operate your instrument.

3.2 Quick Start Programming

Use this section to quickly start up your instrument. This section contains the basic concepts you should
know for configuring the instrument. For more details on specific topics, you should refer to section 4 and
5 of this manual.

Step

Action

See

1

To program analog inputs

Section 4.7 Program Analog Inputs

2

To program control (if your
application has control)

Section 3.14 How to program common configurations
Section 4.8 Program Control Loops
Section 5 Setpoint Profiler (if your instrument has a setpoint profiler)
Section 4.9 Program Analog Outputs

3

To configure displays

Section 4.18 Program Displays

4

To configure data storage

Section 4.26 Data Storage

5

To program other functions

Remaining sections in
Section 4 How To Program Function Blocks and Features

3.3 Modes of Operation

The instrument has three modes of operation: Program, Online, and Maintenance. Each mode has its
own menus. Most menu items provide access to sub-level menus. The SET MODE item switches the
instrument from one mode to another. Your instrument may have reduced menus if options are not
present.

Program mode

Program Mode is an off-line mode for programming (configuring) the instrument. In this mode, all inputs
and outputs are frozen. If any of the five relays are assigned as DAT outputs the recorder will stop
pulsing them when it is placed into Program Mode. The outputs will remain frozen in their present state,
either On or Off.

Online Mode

Online Mode enables full use of the instrument with its inputs, outputs and internal programming. In this
mode, it is fully interactive with all externally connected elements.

Maintenance Mode

Maintenance Mode is an off-line mode for maintaining proper and complete functioning of the instrument.
Functions include calibration, off-line diagnostic testing, and various setups for operation. In
Maintenance Mode, all inputs and outputs are frozen. If any of the five relays are assigned as DAT
outputs the recorder will stop pulsing them when it is placed into Maintenance Mode. The outputs will
remain frozen in their present state, either On or Off.

Advertising