Table 3-9 Function Block Configuration Procedure (continued)

Step

Action

4

Program the function block’s other items as desired. Other items include decimal point positions,
descriptor, tag, and various labels for identifying the function block.

5

Repeat steps 1-4 for all desired function blocks until the instrument is configured.

Example configuration

Figure 3-10 shows a simplified configuration using typical function block connections. Note that several
parameters are left out to simplify the drawing and procedure.

Table 3-10 describes how to program these connections.

A I 1

L P 1

A O 1

P V

L P 1O V

IN P U T

S E T P O I N T # 1 =

1 5 0 0

A L 1

D O 1

A I1 O V

IN P U T

IN P U T

S E T P O I N T = 5 0 0

A L 1 O S

T Y P E = C A T

T Y P E =

T y p e J

D O 1O S

A O 1 O V

A O 1 B C

F E E D B A C K

K E Y

:

F U N C T IO N B L O C K T Y P E
IN P U T P A R A M E T E R

F U N C T IO N B L O C K P A R A M E T E R

P A R A M E T E R C O D E

A C T I O N = H I G H

A I1 O V

Figure 3-10 Example Configuration

Table 3-10 Example Configuration Procedure

Function block type (Full name
as displayed in the Program
menu
)
1. Select this menu item from
the Program menu.

2. Select this
input parameter
from the function
block’s menu...

...and program it
with this output
code. See Section
3.11 for details.

3. Select this
Function block
parameter from the
function block’s
menu...

...and program
it with this
choice. See
Section 3.12
for details.

AI 1 (ANALOG INPUT #1)

-- -- TYPE

TYPE

J

LP 1 (LOOP #1)

PV AI1

OV

SETPOINT#1

1500

FEEDBACK

AO1

BC

AL 1 (ALARM #1)

INPUT AI1

OV SETPOINT

500

ACTION

HIGH

DO 1 (DISCRETE OUTPUT #1)

INPUT AL1

OS --

--

AO 1 (ANALOG OUTPUT #1)

INPUT LP1

OV TYPE

CAT