Installer Test (IT) Mode

To enter Installer Test Mode:

• Press and hold both the Up arrow button and the

Down Arrow button for three (3) seconds.

This displays all segments of the LCD screen on the LCD.

See Fig. 22 on page 10.

17

Setpoint Range

Stop for Cooling

50 to

90

Range is 50°F to 90°F.

Default is 50°F.

18

Keypad Lockout

0

All keys are available (Default)

1

The System button (Heat/Cool) is locked out

2

Both the System and Fan buttons are locked out.

3

All buttons are locked out (System, Fan, Up Arrow,

and Down Arrow). The LCD displays LOCKED.

19

Remote Setback

0

Disabled

1

Hotel card enabled N.O. for unoccupied mode with

1 second software delay going from UnOccupied to

Occupied;

2 minute delay going from Occupied to UnOccupied.

2

Hotel Card enabled N.C. for unoccupied mode with

1 second software delay going from UnOccupied to

Occupied;

2 minute delay going from Occupied to UnOccupied.

3

Hotel Card enabled N.O. for unoccupied mode with

1 second software delay going from UnOccupied to

Occupied;

30 minute delay going from Occupied to

UnOccupied

4

Hotel Card enabled N.C. for unoccupied mode with

1 second software delay going from UnOccupied to

Occupied;

30 minute delay going from Occupied to

UnOccupied.

5

Button Press (Default)

Press and hold “Heat/Cool/

Off” button for 3 seconds

and thermostat will go into

“Economy Setback”

20

Remote Setback for

Heating

50 to

70

Range is 50°F to 70°F.

Default is 64°F.

Used when the thermostat

is in the Unoccupied state.

21

Remote Setback for

Cooling

72 to

90

Range is 72°F to 90°F.

Default is 79°F.

22

Activity Sensing

0

Disabled (Default)

This will be selectable when

ISU 19 is set to option 0 or

5. If ISU 19 is configured

for N.O or N.C, activity

sensing will not be

available.

1

4 hour sensing

2

8 hour sensing

3

12 hour sensing

4

16 hour sensing

5

20 hour sensing

6

24 hour sensing

23

Freeze Protection

0

Disabled

This feature can not

activate when the

application is Cool only.

1

Enabled (Default) – Stat cycles On Heat when room

temperature reaches 40°F (4°C), and disables Heat

when room temperature reaches below 46°F (8°C).

The LCD displays FREEZE PROTECT

24

Auto Fan Reset

0

Inactive (Default)

Auto Fan Reset is not

allowed (does not display)

when the fan control type is

set to Auto Only, (IS code

#9 - value 1).

1

Resets back to Auto after 2 hours. The start time is

calculated after the initial call for Heat/Cool is

satisfied. Then, the two (2) hour timing begins.

2

Resets back to Auto after 4 hours. The start time is

calculated after the initial call for Heat/Cool is

satisfied. Then, the four (4) hour timing begins.

Table 4. Installer Setup (IS) Codes and Options. (Continued)

IS

Code Code Description

Option

Value

Option Description (Default value shown in

Bold)

Notes