TB6575/TB8575 SUITEPRO™ DIGITAL FAN COIL THERMOSTATS

62-0278—07

14

Table 5 provides the Test codes (IT codes) and values. To

enter the IT codes:

1. Press the System (Heat/Cool) button to cycle

through the IT codes, which display in the upper

right above the word Test.

2. Press the Up or Down Arrow buttons to cycle

through the values for the currently displayed IT

code. The values display in the center of the screen.

3. After the desired value displays, press the System

button to store your value selection and display the

next IT code.

NOTE: Exiting Installer Test Mode is the same as the

method for entering test mode,

Fig. 25. Installer Test (IT) mode screen.

OPERATION

PROPORTIONAL + INTEGRAL

(P+I) CONTROL

Like a mechanical thermostat, the fan coil thermostats

have On/Off control output. However, this output is

regulated by a P+I algorithm, enabling the thermostat to

control closer to setpoint than conventional thermostats.

This results in performance where the space temperature

is maintained within 0.75°C (1.5°F) of the setpoint

regardless of fan speed.

NOTE: Integral action corrects the temperature con-

trol errors of proportional-only control, but it

is slower to react to large temperature or set-

point changes.

Economy Setback Modes

ACTIVITY SENSING (IS CODE #22)

If Activity Sensing is enabled, any time the thermostat is

not touched (no single key is pressed) for the duration

selected, the thermostat automatically falls back into the

Economy Setback. The LCD displays ECONOMY

SETBACK just to the right of the main temperature display

to indicate Activity Sensing mode is active. When any key

is pressed, the thermostat controls to Occupied mode.

M27587

Test

Table 5. Installer Test (IT) Codes and Options.

IT

Code

Code

Description

Option

Value

Option Description

10

Heat Control

0

Close

1

Open

20

Auxiliary Heat

Control

0

Close

1

Open

30

Cool Control

0

Close

1

Open

40

Fan Control

0

Close

1

Low Speed

2

Medium Speed

3

High Speed

50

Pipe Sensor

32-199 Displays the pipe

sensor temperature.

Only used for System

Type 3 or 6 (IS code

#2, value 3 or 6). Only

the Analog pipe sensor

is tested.

71

Software Main

version

01-99 A 2-digit number, 01-99

72

Software Vice

version

01-99 A 2-digit number, 01-99

73

Configuration

Data Main version

01-99 A 2-digit number, 01-99

74

Configuration

Data Vice version

01-99 A 2-digit number, 01-99

75

Week Produced

01-52 A 2-digit number, 01-52

76

Year Produced

08-99 A 2-digit number, 08-99