Features, Specifications, Ordering information – Honeywell R7824 User Manual

Page 2

Advertising
background image

R7824, R7847, R7848, R7849, R7851, R7852, R7861, R7886 AMPLIFIERS FOR 7800 SERIES AND R7140 RELAY MODULES

65-0109—14

2

ORDERING INFORMATION

When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the

TRADELINE® Catalog or price sheets for complete ordering number.

If you have additional questions, need further information, or would like to comment on our products or services, please write or

phone:

1. Your local Honeywell Automation and Control Products Sales Office (check white pages of your phone directory).

2. Honeywell Customer Care

1985 Douglas Drive North

Minneapolis, Minnesota 55422-4386

3. http://customer.honeywell.com or http://customer.honeywell.ca

International Sales and Service Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France,

Germany, Japan, Mexico, Netherlands, Spain, Taiwan, United Kingdom, U.S.A.

The R7886A Dynamic Self-Check Ultraviolet Amplifier is a

solid state plug-in amplifier that responds to a pulsed direct

current signal from a C7076A,C Ultraviolet Flame Detector

with adjustable sensitivity to indicate the presence of flame

when used with 7800 SERIES and R7140 Relay Modules.

FEATURES

• Flame failure response time of 0.8 or 1 second; or 2.0

or 3.0 seconds, depending on the amplifier and relay

module selected. See Table 1.

• Plug-in to 7800 SERIES and R7140 Relay Module

through printed circuit board edge connector keyed

for proper orientation.

• Flame signal test jacks measure amplifier flame signal

voltage.

• 0.0 to 5.0 Vdc Flame signal strength reading range.
• Color coded label identifies flame detection type:

— Green—rectification.

Red—infrared.

— Purple—ultraviolet.

Blue—pulsed rectification.

— White—optical.

• R7847B, R7848B, R7849B Dynamic Ampli-Check®

circuitry tests all flame amplifier components 12 times

per minute. The 7800 SERIES and R7140 Relay Module

locks out on safety shutdown with amplifier failure.

• R7824C, R7847C Dynamic Self-Check Rectification

Amplifier, R7851C Dynamic Self-Check Optical Flame

Amplifier, R7861 Self-Check Ultraviolet Flame

Amplifier and R7886A Dynamic Self-Check Ultraviolet

Amplifier test the detectors and all electronic

components in the flame detection system 12 times

per minute. The 7800 SERIES and R7140 Relay Module

locks out on safety shutdown with flame detection

system failure.

NOTE: R7824C, Series 2 or greater and R7847C Series 4

or greater, pulse the shutter when signal of 1.5 Vac

is sensed. Display readings of 0.7 to 2.4 Vdc are

common.

SPECIFICATIONS

Models:

Flame Detection Systems (see Table 2):

Rectification:

R7824C for use with C7024E,F Solid State Ultraviolet

Detectors.

R7847A,B for use with flame rods or C7012A,C Solid State

Ultraviolet Detectors.

R7847C for use with C7012E, F Solid State Ultraviolet

Detectors.

Advertising