R7824, R7847, R7848, R7849, R7851, R7852, R7861, R7886 AMPLIFIERS FOR 7800 SERIES AND R7140 RELAY MODULES

65-0109—14

4

Table 2. Flame Detection Systems.

a

Flame Failure Response Time (FFRT) depends on selection of amplifier and 7800 SERIES and R7140 Relay Module.

b

R7824C is used only with the 24 Vdc RM7824 Relay Module and C7024E,F Flame Detectors.

c

Circuitry tests all electronic components in flame detection system (amplifier and detector) 12 times a minute during burner oper-

ation and shuts down burner if detection system fails.

d

Circuitry tests flame signal amplifier 12 times a minute during burner operation and shuts down burner if amplifier fails.

e

200/220/240 Vac applications require a 120 Vac, 10 VA minimum stepdown transformer (not provided) to drive the shutter. Applies

to R7886A series 2 or greater; R7861 series 1 or greater. Fig. 2 shows flame detector wiring.

f

Use C7027, C7035 and C7044 Flame Detectors only on burners that cycle on-off at least once every twenty-four hours. Use

C7061A Ultraviolet Detector with R7861A Amplifier or C7076A Flame Detector with R7886A Amplifier as ultraviolet flame detec-

tion system for appliances with burners that remain on continuously for twenty-four hours or longer.

g

R7847A,B Amplifiers with 0.8/1 second FFRT should NOT be used with C7012A,C Solid State Ultraviolet Detectors.

h

R7824C Series 2 and greater and R7847C Series 4 or greater, check flame detector system when flame reaches 1.5 Vdc or at

4.5 seconds, whichever occurs first.

NOTE: R7824C Series 2 or greater and R7847C Series 4 or greater, pulse the shutter when signal of 1.5 Vdc is sensed. Display

readings of 0.7 to 2.4 Vdc are common.

i

Order flame rod separately; see flame detector Instructions for holder.

Plug-in Flame Signal Amplifiers

Applicable Flame Detectors

Type

Color

Self-Checking

Model

Flame

Failure

Response

Time (sec)

a

Fuel

Type

Models

Rectification Green

Dymanic Self-

Check

R7824C

b,c,h

3

Gas, oil,

coal

Ultraviolet (Purple

Peeper®)

C7024E,F

No

R7847A

g

0.8/1 or 2/3 Gas

Rectifying Flame Rod
Holders

i

C7004, C7007, C7011

Complete Assemblies:

C7008, C7009, Q179

No

R7847A

g

2/3

Gas, oil,

coal

Ultraviolet (Purple

Peeper®)

C7012A,C.

Dynamic Ampli-

Check®

R7847B

d,g

0.8/1 or

2/3

Gas

Rectifying Flame Rod
Holders

i

C7004, C7007, C7011

Complete Assemblies:

C7008, C7009, Q179

Dynamic Ampli-

Check®

R7847B

d,g

2/3 Gas,

oil,

coal

Ultraviolet (Purple

Peeper®)

C7012A,C

Dynamic Self

Check

R7847C

c,h

3

Gas, oil,

coal

Ultraviolet (Purple

Peeper®)

C7012E,F

Infrared

Red

No

R7848A

2/3

Gas, oil,

coal

Infrared (Lead

Sulfide)

C7015

Dynamic Ampli-

Check®

R7848B

d

2/3

Gas, oil,

coal

Infrared (Lead

Sulfide)

C7015

Red/

White

No

R7852A

2/3

Gas, oil,

coal

Infrared (Lead

Sulfide)

C7915

Dynamic Ampli-

Check®

R7852B

b

2/3

Gas, oil,

coal

Infrared (Lead

Sulfide)

C7915

Ultraviolet

Purple No

R7849A

0.8/1 or

2/3

Gas, oil Ultraviolet

(Minipeeper)

C7027, C7035, C7044

f

Dynamic Ampli-

Check®

R7849B

d

0.8/1 or

2/3

Gas, oil Ultraviolet

(Minipeeper)

C7027, C7035, C7044

f

Dynamic Self-

Check

R7861A

c,e

0.8/1 or

2/3

Gas, oil,

coal

Ultraviolet

C7061

Blue

Dynamic Self-

Check

R7886A

c,e

2/3

Gas, oil,

coal

Ultraviolet (Adjustable

Sensitivity)

C7076

Optical

White

Dymanic Ampli-

Check®

R7851B

0.8/1 or 2/3 Gas, oil,

coal

Optical (UV, Visible

Light)

C7927, C7962

Dynamic Self-

Check

R7851C

c

2/3

Gas, oil,

coal

Optical (UV only)

C7961