R7824, R7847, R7848, R7849, R7851, R7852, R7861, R7886 AMPLIFIERS FOR 7800 SERIES AND R7140 RELAY MODULES

5

65-0109—14

CAUTION

Equipment Damage Hazard.

Incorrect combination of relay module, amplifier

and flame detector can cause equipment damage.

In infrared applications (C7015 Infrared Flame Detector

and R7848 Amplifier) using the RM7890 Relay Module

with software version 4004 or less requires a ten-

second delay to start sequence. This applies only to the

initial power of the RM7890.

INSTALLATION

When Installing this Product...

1. Read these instructions carefully. Failure to follow them

could damage the product or cause a hazardous condition.

2. Check the ratings given in the instructions and on the

product to make sure the product is suitable for your

application.

3. Installer must be a trained, experienced, flame safeguard

control technician.

4. After installation is complete, check out the product oper-

ation as provided in these instructions.

WARNING

Electric Shock Hazard.

Can cause electrical shock, serious injury or death.

Disconnect the power supply before beginning

installation. More than one power supply disconnection

can be involved.

IMPORTANT

1. Wiring must comply with all applicable codes, ordi-

nances and regulations

2. Wiring (where required) must comply with NEC Class

1 (Line Voltage) wiring.

3. Perform all required checkout tests after installation is

complete.

CAUTION

Equipment Damage Hazard.

Can cause equipment damage.

Disconnect 7800 SERIES and R7140 Relay Module

power before removing amplifier.

Installing Plug-In Flame
Signal Amplifier (Fig. 2)

WARNING

Electric Shock Hazard.

Can cause severe injury, death or property damage.

Disconnect the power supply before beginning

installation. More than one power supply disconnection

can be involved.

1. Align the amplifier circuit board edge connector with the

keyed receptacle on the 7800 SERIES and R7140 Relay

Module. Be sure the amplifier nameplate faces away

from the Relay Module.

2. Push in the amplifier until the circuit board is fully

inserted into the receptacle and then push the amplifier

toward the 7800 SERIES and R7140 Relay Module

retaining clasp.

3. Be sure the amplifier is firmly in place.

4. Perform all required checkout tests.

Installing Flame Detector

NOTE: Table 2 lists flame detection systems available for use

with 7800 SERIES and R7140 Relay Modules. Be

sure to use the correct combination of amplifier and

flame detector.

Proper flame detector installation is the basis of a safe and

reliable flame safeguard installation. Refer to the Instructions

packed with the flame detector and the equipment

manufacturer instructions.

Keep the flame signal leadwires as short as possible from the

flame detector to the wiring subbase. Capacitance increases

with leadwire length, reducing the signal strength. The

maximum permissible leadwire length depends on the type of

flame detector, leadwire and conduit. However, the ultimate

limiting factor for the flame detector leadwire is the flame

signal; see Table 3 in the Checkout section.

Fig. 2. Installing flame signal amplifier.

Wiring

WARNING

Electrical Shock Hazard.

Can cause severe injury, death or property damage.

Disconnect power supply before beginning installation.

More than one disconnection can be involved.

5. Remove the 7800 SERIES and R7140 Relay Module

from the wiring subbase.

6. Refer to Fig. 3 for proper flame detector wiring.