APPLICATION

The T8524C, D Multistage Microelectronic Thermostat provides electronic control of 24 Vac two-stage heating and two-
stage cooling systems. Refer to Table 1 for a general description of the thermostat. All T8524 Thermostats require a
common wire to supply power.

Table 1. Description of T8524 Thermostats.

RECYCLING NOTICE

If this control is replacing a control that contains
mercury in a sealed tube, do

not

place your old

control in the trash.

Contact your local waste management authority for
instructions regarding recycling and the proper
disposal of the old thermostat.

INSTALLATION

When Installing this Product...

1. Read these instructions carefully. Failure to follow

the instructions can damage the product or cause a
hazardous condition.

2. Check the ratings given in the instructions and on

the product to make sure the product is suitable for
your application.

3. Installer must be a trained, experienced service

technician.

4. After completing installation, use these instructions

to check out the product operation.

CAUTION

Disconnect power supply to prevent electrical
shock or equipment damage.

Location

Install the thermostat about 5 ft (1.5m) above the floor in
an area with good air circulation at average temperature.
See Fig. 1.

Do not install the thermostat where it can be affected by:

drafts, or dead spots behind doors and in corners.

hot or cold air from ducts.

radiant heat from sun or appliances.

concealed pipes and chimneys.

unheated (uncooled) areas such as an outside wall
behind the thermostat.

Wallplate Installation

The thermostat can be mounted horizontally on the wall or
on a 2 in. x 4 in. wiring box. Position wallplate horizontally
on the wall or on a 2 in. x 4 in. wiring box.

1. Position and level the wallplate (for appearance

only). The thermostat will function properly even
when not level.

T8524

System

Changeover

System

Selection

Fan

Selection

Comments

C

Heat-Cool

Manual

Heat-Off-Cool

On-Auto

System and fan selections are done by
switches.

D

Heat-Cool

Automatic

Heat-Off-Cool-Auto

On-Auto

System and fan selections are done by
keyboard.