The time is entered in increments

of 10 minutes in each case .

Important: The times must be entered

in ascending order.

E03

Alarm temperature difference

–50 K to + 50 K

20 K

E04

Delay time – Alarm

0 to 99 mins.

10 mins.

E05

Compressor start-up delay

0 to 15 mins.

5 mins.

E06

Defrost type

1 or 2

1

1 = Electrical (compressor off)
2 = Hot gas (compressor on)

E07

Defrost limit temperature

0 to 50 °C

8 °C

E08

Defrost time limit

1 to 99 mins.

25 mins.

E09

Drainage time, evaporator

0 to 99 mins.

3 mins.

E10

Time delay, fan

0 to 500 secs.

30 secs.

E11

Evaporator fan control

1,2 or 3

1

1 = Fan with compressor.
2 = Continuous fan operation, except during defrosting.
3 = Fan run-on. If there is an undershoot in the cold

store temperature, the fan is switched on by
evaporator sensor T2. The fan is switched off again
once the desired cold store temperature is
attained or exceeded.

E12

Minimum permissible

–55 °C to E13

–55 °C

cold store temp.

E13

Maximum permissible

E12 to +50 °C

+50 °C

cold store temp.

E14

Display during defrosting

1,2 or 3

1

1 = “dEF” in display.
2 = Current cold store temperature in display.
3 = Retaining temperature in display when defrosting

is initiated until the current cold store temperature
reaches the retained value again. This is for a maxi-
mum of 15 minutes after the end of defrosting.

(

Evaporator drainage time E09 and time delay fan E10 are not
respected at hot gas defrost mode E06 = 2.