Heat & Glo • 350TRSI-AUF, 350TRSILP-AUF • 2089-980 Rev. R • 2 /13

Figure 7.4

Top Vent - Horizontal Termination

Note: A 6 in. (152 mm) section of straight flue must

be attached to the heater before a 90° elbow.

Fire Risk. Explosion Risk.
Do NOT pack insulation or other combustibles

between ceiling firestops.
• ALWAYS maintain specified clearances around

venting and firestop systems.

• Install wall shield and ceiling firestops as speci-

fied.

Failure to keep insulation or other material away

from vent pipe may cause fire.

WARNING

V

1

Minimum

H

1

Maximum

Elbow only

NOT ALLOWED

1 ft.

305 mm

2 ft.

610 mm

2 ft.

610 mm

4 ft.

1.22 m

3 ft.

914 mm

8 ft.

2.44 m

4 ft.

1.22 m

10 ft.

3.05 m

5 ft.

1.52 m

16 ft.

4.88 m

V

1

+ H

1

= 30 ft. (9.14 m) Maximum

H

1

V

1

USE SLP SERIES COMPONENTS ONLY

Example: DVP pipe 3 ft. (1 m) min. vertical = 11 ft. (3.35 m)

max. horizontal

SLP pipe 7 ft. (2.13 m) min. vertical = 11 ft. (3.35

m) max. horizontal