C. install the ceiling firestop – Heat & Glo Fireplace Heat & Glo 350TRSILP-AUF User Manual

Page 39

Advertising
background image

39

Heat & Glo • 350TRSI-AUF, 350TRSILP-AUF • 2089-980 Rev. R • 2 /13

C. Install the Ceiling Firestop

A ceiling firestop

MUST be used between

floors and attics.

DVP pipe only - Frame an opening 10 in. x

10 in. (254 mm by 254 mm) whenever the

vent penetrates a ceiling/floor (see Figure

8.3).

SLP pipe only - Frame opening 9 in. x 9

in. (229 mm x 229 mm) whenever the vent

penetrates a ceiling/floor (see Figure 8.3).

• Frame the area with the same sized lumber

as used in ceiling/floor joist.

• The ceiling firestop may be installed above or

below the ceiling joists when installed with a

attic insulation shield. It must be under joists

between floors that are not insulated. Refer

to Figure 8.4.

• Secure with three fasteners on each side.
WARNING! Risk of Fire! DO NOT pack insu-

lation around the vent. Insulation must be kept

back from the pipe to prevent overheating.

Figure 8.3 Installing Ceiling Firestop

Figure 8.4 Installing the Attic Shield

3 FASTENERS

PER SIDE

INSTALL ATTIC INSULATION SHIELDS

BEFORE OR AFTER INSTALLATION OF VENT SYSTEM

CEILING FIRESTOP

INSTALLED BELOW CEILING

CEILING FIRESTOP

INSTALLED ABOVE CEILING

ATTIC ABOVE

A

PIPE
DVP
SLP

A

10 in. (254 mm)

9 in. (229 mm)

A