H. flue termination – Heat & Glo Fireplace Heat & Glo 350TRSILP-AUF User Manual

Page 49

Advertising
background image

49

Heat & Glo • 350TRSI-AUF, 350TRSILP-AUF • 2089-980 Rev. R • 2 /13

Figure 10.15 Ceiling Firestop (Ceiling Side)

Figure 10.16 Attic Firestop

CEILING

CEILING FIRESTOP

RAFTER

NAILS (4 REQUIRED)

JOIST

CEILING FIRESTOP

CEILING

NAILS (4 REQUIRED)

If the area above the ceiling

IS an attic, position and secure

the firestop on top of the previously framed hole.

If the area above the ceiling is

NOT an attic, position

and secure the ceiling firestop on the ceiling side of the

previously cut and framed hole.

Figure 10.17 Venting through the Wall

• The termination kit should pass through the wall firestops

from the exterior of the building.

• Adjust the termination cap to its final exterior position on

the building and interlock the flue sections.

WARNING! Risk of Fire! the termination cap must be

positioned so that the arrow is pointing up.
• Use a high-temperature sealant gasket to seal between

the pipe and exterior firestop.

EXTERIOR

INTERIOR

Interior

Wall Shield

Inner Flue

Rear Flue

Heat Shield

1-1/2 in.

(38 mm min)

overlap

Outer Flue

H. Flue Termination

For Horizontal Terminations using the SLP-TRAP2 or

DVP-TRAP2
To attach and secure the termination to the last section of

horizontal flue:
• The rear flue heat shield MUST be placed one inch above

the top of the flue between the wall shield and the base

of the termination cap.

• One section of the heat shield is attached to the wall

shield. The other is attached to the termination cap in

the same manner (see Figure 10.17).

• The heat shield sections will overlap to match the wall

thickness (depth).

• If the wall thickness does not allow the required 1-1/2 inch

(38 mm) heat shield overlap, an extended heat shield

must be used. The extended heat shield will need to be

cut to the thickness of the wall and be attached to the

wall shield.

• The small leg in the shield rests on top of the flue to

properly space it from the pipe section (see Figure 10.17).

Figure 10.18 Termination Cap

1 in. (25 mm)

7-1/2 in.

(192 mm)

MINIMUM

Cap Specification Chart

(depth without using additional pipe sections)

350TRSI-AUF

350TRSILP-AUF

DVP-TRAP2 / SLP-TRAP2

Rear Vent Depth

5-1/2 in. (152 mm) to 9-1/2 in. (241 mm)