CHECKOUT

For best results, allow the sensor to absorb the air
moving through the room for a minimum of twenty
minutes before taking a resistance measurement.

1. Use an accurate thermometer (+/-1ºF[0.5ºC]) mea-

sure the temperature at the sensor location.

2. Remove one wire from one of the sensor's wiring

terminals. Use an ohmmeter to measure the resis-
tance across the sensor. Verify the sensor accu-
racy with the temperature/resistance in Table 1.

CALIBRATION

The sensor is calibrated at the factory and cannot be
recalibrated in the field.

Table 1. Sensor Resistance at Room Temperature.

Room Temperature

Ohms of

Resistance

°F

°C

40

4.4

22537

42

5.6

21516

44

6.7

20546

46

7.8

19626

48

8.9

18754

50

10.0

17926

52

11.1

17136

54

12.2

16387

56

13.3

15675

58

14.4

14999

60

15.6

14356

62

16.7

13743

64

17.8

13161

66

18.9

12607

68

20.0

12081

70

21.1

11578

72

22.2

11100

74

23.3

10644

76

24.4

10210

78

25.6

9795

80

26.7

9398

82

27.8

9020

84

28.9

8659

86

30.0

8315

88

31.1

7986

90

32.2

7672

92

33.3

7372

94

34.4

7086

96

35.6

6813

98

36.7

6551

100

37.8

6301