W7340, W7345 COMMUNICATING ECONOMIZER LOGIC MODULES

11

63-2569—04

TROUBLESHOOTING

The status LED is visible through a hole in the device cover. A

priority-based LED flash sequence indicates a detected fault.

0.25 seconds elapses between each pulse, a higher pulse

count indicates higher priority. A two-second on period

precedes each repeated sequence.

The diagnostic bit position corresponds to the Modbus

diagnostic register. The diagnostic bit resets when the

respective fault is present. To read all active faults, read the

diagnostic register via Modbus function code 8 (no flash

priority needed).

NOTES:

All pulse counts (Table 4) are based on the

number of times the light pulses off.

In the event of a Communications Failure, the LED

pulses on for 0.25 seconds every 2 seconds.

Table 4. W7340 Economizer Checkout.

Description

Pulse

count

Diagnostic

bit

Booting (0-3 min. after power-up)

NA

12

Mixed air temperature sensor fault

8

7

Outdoor air temperature sensor fault

7

6

Outdoor air humidity sensor fault

6

5

Return air temperature sensor fault

4

3

Return air humidity sensor fault

3

2

Indoor air quality sensor fault

2

1

Actuator fault

1

0

Proper operation (outdoor air

appropriate for free cooling)

Solid

ON

NA

Proper operation (NO free cooling)

2 Hz flash

NA

Communications failure

1 (pulses

on)

NA