Installation, When installing this product, Location and mounting – Honeywell W7340 User Manual

Page 3: Communicating economizer logic modules, Mounting directly to the motor, Mounting separate from the motor, Caution

Advertising
background image

W7340, W7345 COMMUNICATING ECONOMIZER LOGIC MODULES

3

63-2569—04

Table 1. Logic Module Inputs and Outputs.

a

2-wire (18, 20, 22 AWG) connection.

INSTALLATION

When Installing this Product...

1. Read these instructions carefully. Failure to follow them

could damage the product or cause a hazardous

condition.

2. Check the ratings given in the instructions and on the

product to make sure the product is suitable for your

application.

3. Installer must be a trained, experienced service

technician.

4. After installation is complete, check out product

operation as provided in these instructions.

IMPORTANT

All wiring must agree with applicable codes,

ordinances and regulations.

CAUTION

Electrical Shock or Equipment Damage Hazard.

Can shock individuals or short equipment

circuitry.

Disconnect power supply before installation.

Location and Mounting

Communicating Economizer Logic Modules

When planning the installation, allow enough clearance for

maintenance and service. Mount the device in a location

protected from rain, snow, and direct sunlight. The logic

module mounts on the side of an M7215 Damper Motor or

directly on a sheet metal duct or panel.

NOTE: Refer to Figures 4 and 5 for representative locations

of connected system devices.

CAUTION

Equipment Damage Hazard.

Mounting screws longer than 5/8 in. can damage

internal motor components.

When mounting the module to an M7215 use only the

included #6 5/8 in. thread-forming screw.

MOUNTING DIRECTLY TO THE MOTOR

1. Mount the motor.

2. Secure the W7340 or W7345 to the motor using the

supplied mounting screw (See Fig. 2).

MOUNTING SEPARATE FROM THE MOTOR
Secure the device to the sheet metal using appropriate

fasteners (not supplied)(See Fig. 3).

Fig. 2. Mounting Economizer Logic Module on Damper

Motor.

W7340

W7345

Inputs

Enthalpy

4-20 mA

a

Modbus

yes

yes

Return Sensor

optional

Mixed/Discharge Air

10K ohm

a

10K ohm

a

Outdoor Sensor

10K ohm

a

Indoor DCV Sensor

0-10 Vdc control signal

Remote Minimum

Position Potentiometer

optional

optional

Motor Feedback

2-10 Vdc

Outputs
Modbus

yes

yes

Exhaust

One set of 24 Vac

contacts (spst)

Motor Output Signal

2-10 Vdc

M17550B

ECONOMIZER

LOGIC MODULE

M7215

DAMPER

MOTOR

5/8 INCH SCREW INCLUDED

WITH LOGIC MODULE.