Enthalpy sensor (w7340 only), Outdoor air sensing, Return air sensing – Honeywell W7340 User Manual

Page 4: Dcv min and min position damper set up

Advertising
background image

W7340, W7345 COMMUNICATING ECONOMIZER LOGIC MODULES

63-2569—04 4

Fig. 3. Mounting to a Duct or Panel.

Enthalpy Sensor (W7340 only)

To measure enthalpy, the logic module accepts signals from

either:

— C7600C Humidity and 10K NTC temperature sensors.

— or a C7400 Enthalpy Sensor.

IMPORTANT

• When using C7400 Enthalpy Sensors, connect the

enthalpy sensors to the humidity sensor terminals;

leave the temperature sensor terminals empty.

• Use C7400A sensor with W7340A or W7340B.

• Use C7400C sensor with W7340C.

OUTDOOR AIR SENSING

1. Mount each sensor in any orientation that exposes it to

freely circulating air and protects it from rain, snow, and

direct sunlight.

2. Connect it to the logic module.

RETURN AIR SENSING

1. For differential enthalpy or temperature control mount a

second sensor in the return air duct.

2. Connect it to the logic module.

Demand Control Ventilation (DCV) Sensor Input
(W7340 only)

The DCV sensor can be any sensor that provides a 0-10 Vdc

output over a range of 0 to 2000 ppm of CO

2

. The DCV signal

modulates the outdoor damper to provide ventilation based on

occupancy. Mount the sensor according to the manufacturer

specifications. If not available, mount the sensor in an area

with unobstructed air circulation.

IMPORTANT

• Ensure proper polarity of sensor connections.

Incorrect polarity negates the sensor signal.

W7340B: The W7340B DCV economizer logic modules

incorporate a minimum position setting that defaults to 20%,

but can be overridden using the Modbus communication link.

The W7340B DCV maximum position sets the damper position

to a position that the damper goes to if the CO

2

sensor fails. If

the minimum position set point is higher than the DCV

maximum position, on sensor failure, the damper goes to the

higher of the two DCV maximum and minimum position setting.

There is no limit on the damper position on a call from the CO

2

sensor (DCV); the damper can go 100% open.

W7340C: The W7340C DCV economizer logic module has the

ability to set DCV minimum damper position and minimum

position. The DCV minimum position is set to ventilate the

building contaminants and the minimum position is set to

ventilate for the building contaminants and the building

occupants. The installer sets the damper DCV minimum

position and the minimum position based on the design

occupancy and CFM of outdoor air requirements for the space.

The damper will modulate open between the DCV minimum

damper position and the minimum position based on input

from a CO

2

sensor. The damper will not drive 100% open on a

call for ventilation, but can drive 100% open on a call for

cooling. If the CO

2

sensor fails the damper will drive to the

minimum position ventilating for building contaminants and

the building occupants. If the DCV minimum position has not

been set using the following procedure, the default setting will

be 50% of the minimum position setting.

DCV Min and Min Position Damper Set Up

Set up instructions for W7340C DCV damper positions:

1. Remove RAT sensor from RAT terminals.

2. Connect CO

2

sensor to DCV terminals.

3. Apply power to economizer logic module.

4. Wait 10 to 15 seconds for the CO2 sensor to initialize.

Short RAT terminals.

5. Remove CO

2

sensor from DCV terminals.

6. DCV LED will blink 2 times. If LED does not blink, cut

power to economizer logic and repeat steps 1-5.

7. Set DCV minimum position using MIN POS/DCV MIN

potentiometer.

8. Remove RAT short.

9. DCV minimum position is saved to memory and DCV

LED blinks 5 times.

10. Turn off power to economizer logic module.

11. Connect RAT sensor.

12. Turn power on to economizer logic module.

13. Set minimum position using MIN POS/DCV MIN

potentiometer.

IMPORTANT

Steps 3-8 must be completed within 3 minutes after

power up otherwise the configuration process will be

terminated, no changes will be saved and you will

need to repeat steps 1-13.

M17638