W7340, W7345 COMMUNICATING ECONOMIZER LOGIC MODULES

63-2569—04 8

W7340

Potentiometers with screwdriver adjustment slots, located on

the face of the device, provide adjustments for several

parameters (See Fig. 9 for locations on device):

— DCV minimum and minimum damper position.

— Enthalpy changeover.

— DCV setpoint.

Fig. 9. Location of W7340 potentiometers and LED.

IMPORTANT

Before powering the device read the following Enthalpy

changeover setpoint guidelines:

1. Using the Enthalpy changeover setpoint, the setpoint

can be adjusted until three minutes after powering the

device. until three minutes after powering the device.

2. Through the Modbus, the Enthalpy changeover

setpoint can be modified at any time.

3. If the Enthalpy changeover potentiometer is changed

after the three minute power-up time, no change to

the Enthalpy changeover setpoint will occur unless

power is removed from the device then reapplied.

NOTES:

The DCV setpoint can be changed at anytime by

adjusting the pot.

For Enthalpy changeover setpoint see comments

above.

MIN POS can be changed anytime by adjusting

the pot.

DCV Min can be changed by procedure on page 4.

Demand Control Ventilation (DCV) Setpoint

The logic module modulates the outdoor damper to provide

ventilation based on the 2-10 Vdc DCV sensor. With no cooling

signal, DCV overrides the DCV minimum damper position

when ventilation requires outdoor air.

Table 2. W7340 Economizer I/O Logic.

a

For single enthalpy control, the module compares outdoor

enthalpy to the ABCDE setpoint.

b

If both stages of cooling are off, the system is off and the

damper is:

• At DCV minimum position if DCV is below setpoint.

• Modulating if DCV is above setpoint.

c

Modulation based on mixed air sensor signal, modulating

between DCV minimum position and 100% open.

d

Modulation based on DCV signal, limited by minimum

position.

e

Modulation based on the greater of the DCV and mixed air

sensor signals.

Adjusting Minimum Damper Position

The minimum position potentiometer maintains the minimum

outdoor air flow into the building during occupied period.

NOTE: If the mixed air temperature drops to 45° F (7° C), the

mixed air sensor overrides the DCV sensor and

closes the damper to DCV minimum position to

protect the hot or chilled water coils from freezing.

When the mixed air temperature rises to 48° F (9° C),

control reverts to normal operation.

For detailed assistance in minimum position selection,

reference the Economizer Application Guide (form 63-8594)

Ventilation section. The following provides basic guidelines for

minimum position selection and adjustment:

IMPORTANT

1. Adjust the minimum position potentiometer to allow

the amount of outdoor air, as required by local codes,

to enter the building for building contaminants and the

maximum building occupants.

2. This procedure requires use of a quality thermometer

capable of reading to 0.5° F (0.-17.5° C).

NOTE: Make minimum position adjustments with at least a

10° F (-12° C) temperature difference between

outdoor and return air.

See section on DCV setpoint set up on page 4.

P

P1

+

-

+

-

ExF

MAT

OAH

OAT

RAT

RAH

DCV

2-10 VDC

DAMPER

POSITION

2-10 VDC

DAMPER

POSITION

OVERRIDE

MIN POS/

DCV MIN

OPEN

DCV

SETPOINT

1500

500

STATUS LED

DEMAND

CONTROL

VENTILATION

SETPOINT

ENTHALPY

CHANGEOVER

SETPOINT

MIN POS/DCV

MIN DAMPER

POSITION

M23878

MBUS-

MBUS+

TR1 24V COM

TR 24V AC

C

B

E

A

D

+
_

+
_

INPUTS

OUTPUTS

DCV

Enthalpy

a

Y1

b

Y2

b

Compressor

Damper

Outdoor Return

Stage 1 Stage 2

Below

set

High

Low

On On On

On

Minimum

position

On Off

On

Off

Low

High

On On On

Off

Modulating

c

On Off

Off

Off

Above

set

High

Low

On On On

On

Modulating

d

On Off

On

Off

Low

High

On On On

Off

Modulating

e

On Off

Off

Off