EXCEL 500/600 INSTALLATION INSTRUCTIONS

XC5010C / XC6010 Cable Lengths and Sizes

A cable length of 1300 ft (400m) with a cross sectional area of
0.5 mm

2

(20 AWG) is permissible for a two-core, 0 to 10 Vdc

Table 3. Cable sizing

signal cable.

Type of signal

Cross sectional area

≤≤≤≤ 300 ft

(100 m)

≤≤≤≤ 550 ft

(170 m)

≤≤≤≤ 1300 ft

(400 m)

24 Vac power
supply

≤ 16 AWG

(

≥ 1.5 mm

2

)

≤ 14 AWG

(

≥ 2.5 mm

2

)

-

Low voltage
signals

1

≤ 20 AWG (≥ 0.5 mm

2

)

1

0 to 10V sensors, totalizers, digital inputs, 0 to 10V signals for

actuators, etc.

Lightning Protection

Please contact your local Honeywell representative for
information on lightning protection.

MAX. 1300 ft (400 m)

EXTERNAL

TRANSFORMER

MIN. 20AWG (0.5 mm2)

24 Vac

230 Vac
120 Vac

PRIMARY

VOLTAGE

TRANSFORMER

PRIMARY
VOLTAGE

Y

24 Vac

24 V

Y

GND

Fig. 44. Connection of XL500/600 controller and a 24 V

actuator with separate transformers