EXCEL 500/600 INSTALLATION INSTRUCTIONS

Summary of Internal Modules

Table 4. Summary of Excel 500/600 internal modules

Module

Name

Inputs

Outputs

Manual override switches

LED display

Computer module

XC5010C,
XC5210C

Reset button
L

ON

W

ORKS

service button

RS232 front-rear switch

L

ON

W

ORKS

Service LED

C-Bus transmit
C-Bus receive
Normal
System error
RS232 transmit
RS232 receive
Ground loop error

Computer module

XC6010

Reset button

Normal
System error
RS232 transmit
RS232 receive
C-Bus transmit
C-Bus receive

Power supply module

XP502

1

0 (1 x)

Power supply
Watchdog
ext. battery operation

Analog input module

XF521A

8

Analog input module

XF526

8

CPU active

Analog output module

XF522A

8

0 (5 x)
1
Auto

8 x Output intensity

Analog output module

XF527

8

8 x Output intensity

Digital input module

XF523A

12

12 x Status, invertible

Digital output module

XF524A

5 changeover
1 NO contact

0 (5 x)
1
Auto

6 x Status

Digital output module

XF529

5 changeover
1 NO contact

6 x Status

Three-position output
module

XF525A

3 three-position

+ (3 x)
0
-
Auto

3 x Open Close

C-bus repeater (10 KBit)

XD509

NOTE: With XC6010 CPU only, there are submodules for system bus combination, XD505A (10 KBit) / XD508 (1 MBit), and

for stand-alone modem communication, XDM506.