EXCEL 500/600 INSTALLATION INSTRUCTIONS

Line Power Supply

WARNING

A separate CRT 6 or 1450 series (U.S.) transformer must be
used for each of the EXCEL 500/600 controller's 24 V supply.
No additional loads may be connected !
Each additional XL500/600 controller requires its own
transformer.
An additional transformer, appropriate to the power require­
ments, should be used to power input/output peripherals (e.g.
actuators).

MAX. 1300 ft (400 m)

MIN. 20 AWG (0.5 mm2)

PRIMARY
VOLTAGE

EXTERNAL

TRANSFORMER

24 Vac

230 Vac
120 Vac

PRIMARY

VOLTAGE

TRANSFORMER

Y

24 Vac

24 V

Y

GND

Fig. 45. Connection of XL500/600 controller and a 24V

actuator with separate transformers

Primary

Secondary

220 VAC

230 VAC

+ 6 %

-10 %

+10 %

-15 %

24 VAC ±20%

CB-0039a

Fig. 46. Excel 500/600 power supply

To avoid interference, the cable between the transformer and
the power supply module should be kept as short as possible
(max. 6 ft (2m)). The transformer should therefore be
positioned close to the power supply module.
Fuse the transformer primary with its own fast-acting 10 A
back-up fuse (or H 16 or L 16 miniature circuit breaker).
The primary coil of the CRT 6 contains a 0.8 A / 250 V quick­
blow fuse.
Table 5 gives an overview of the transformers of the 1450
series (U.S.):

Table 5. 1450 series transformers data

Part #

1450 7287

Primary

side

Secondary side

-001

120 Vac

24 Vac, 50 VA

-002

120 Vac

2 x 24 Vac, 40 VA, and 100 VA
from separate transformer

-003

120 Vac

24 Vac, 100 VA, and 24 Vdc;
600 mA

-004

240/220 Vac 24 Vac, 50 VA

-005

240/220 Vac

2 x 24 Vac, 40 VA, and 100 VA
from separate transformer

-006

240/220 Vac

24 Vac, 100 VA, and 24 Vdc;
600 mA

The 1450 series includes built-in fuses, line transient /surge
protection and AC convenience outlet, it meets NEC class 2
requirements.

XC6010 Computer Module

CAUTION

Do not unplug the computer module with the power
still connected, since this could destroy the module.
First, switch S1 on the power supply module to the 0
position.

If one of the C-bus submodules XD505A or XD508 is installed
on the XC6010, follow Fig. 47.

Fig. 47. Excel 600 CPU module C-Bus connections

The system bus is connected to terminal 16 (C+) and terminal
17 (C-). See also section "C-Bus Termination (Excel 600)" on
page 38.
If the XDM506 Modem Submodule is installed on the
XC6010, follow Fig. 48. Use the XW571 modem cable to
connect the appropriate modem to the wiring terminals.

23

EN1R-1047GE51 R0902