EXCEL 500/600 INSTALLATION INSTRUCTIONS

Fig. 54. Connection of XAPU 24-2F UPS (internal

modules)

LED (L3) shows operation by battery.

NOTE: The output from the XAPU 24-2F must not be

connected with other devices.

The fully-equipped Excel 500/600 controller will be completely
supported with the battery for at least 15 minutes, without the
mains power 230 Vac.

XP502 with External UPS XAPU 24-2F (Distributed
I/O Modules, Only)

The wiring diagram below is for Excel 500 installations using
only Distributed I/O modules. No internal I/O modules may be
used. No other devices may be connected to the XAPU 24­
2F.

Fig. 55. Connection of XAPU 24-2F UPS (Distributed I/O

modules)

NOTE: There must be no connection between GND of the

XC5010C CPU module and the GND of Distributed
I/O modules.

Relay K1 insures that the supply of the Distributed I/O
modules will be switched OFF by switching OFF the XP502
Power Supply module.
The power consumption of the Excel 500 controller is shown
in the table below. For the power consumption of Distributed
I/O modules, please refer to the corresponding Product Data
(EN0B-0090GE51)

Table 6. Power consumption of Excel 500 controller

Devices powered

Supply voltage

24 Vdc

28.8 Vdc

XP502, XC5010C,
XI581 (backlight ON)

170 mA

155 mA

XP502, XC5010C

140 mA

130 mA

EN1R-1047GE51 R0902