EXCEL 500/600 INSTALLATION INSTRUCTIONS

XP502 with External UPS XAPU 24-2F (Distributed
I/O and Internal Modules)

As shown in the figure below, two XAPU 24-2F UPSs are
required when the controller has both internal and Distributed
I/O modules connected.

Fig. 56. Connection of XAPU 24-2F UPS (internal and

Distributed I/O modules)

XAPU 24-2F number 1 is connected to the XP502 for the
controller, only. No other devices may be powered by XAPU
number 1.
XAPU 24-2F number 2 is connected to the XSL511
L

ON

W

ORKS

connector modules for powering the Distributed

I/O modules. The connection through relay K1 of the XP502
insures that the power supply to the Distributed I/O modules
will be switched OFF when the XP502 is switched OFF.

XF521A Analog Input Module

Technical Specifications
Number:

eight inputs (AI1 – AI8)

Input:

0...10 Vdc (low-input impedance, 25kOhm to 10 V /
200kOhm to GND);
0...20 mA (via external 500-ohm resistor);
4...20 mA (via external 500-ohm resistor);
NTC 20K ohm (-50...+150 °C);
PT1000 (-50...+150 °C)

Protection:

up to 40 Vdc / 24 Vac

Resolution:

12-bit resolution

Accuracy:

±75 mV or 0.75% (0...10 V)

Table 7. Accuracy of analog input sensors

Measurement error (without

Range

sensor tolerance)

PT1000

NTC 20K

-58...-4 °F (-50...-20 °C)

≤ 1.2 K

≤ 5.0 K

-4...+32 °F (-20...0 °C)

≤ 0.7 K

≤ 1.0 K

+32...86 °F (0...30 °C)

≤ 0.5 K

≤ 0.3 K

86...158 °F (30...70 °C)

≤ 0.7 K

≤ 0.5 K

158...212 °F (70...100 °C)

≤ 1.2 K

≤ 1.0 K

212...266 °F (100...130 °C)

≤ 1.2 K

≤ 3.0 K

266...302 °F (130...150 °C)

≤ 1.2 K

≤ 5.5 K

With current sensors, a terminating resistor of R1 = 499 ohms
± 0.25 % must be connected.
Terminal 18 is an auxiliary output voltage (+10 Vdc, I

max

=

5 mA) available for various sensor circuits.

Fig. 57. XF521A Analog Input module connections

27