Honeywell Excell 500/600 Controll System 500-XCL5010 User Manual

Page 30

Advertising
background image

EXCEL 500/600 INSTALLATION INSTRUCTIONS

XF522A and XF527 Analog Output Modules

Technical Specifications
Number:

8 analog outputs

Voltage rating:

0 to 10 V, max. 11V

Current rating:

1 mA max.

Resolution:

8 bit

Accuracy:

±150 mV or 1.5% deviation from output voltage

Manual override switches:

XF522A

5 manual override switches (AO1 to AO5)

XF527

No manual override switches

Fig. 63. XF522A and XF527 Analog Output modules

NOTE: The maximum output current of 1 mA must not be

exceeded.

NOTE: Both modules are fully pin compatible.

XF524A and XF529 Digital Output Modules

Technical Specifications
Number:

6 digital outputs

Voltage rating:

240 Vac max. per contact and per module

Current rating:

4 A max. per contact, 12A max. per module

Relay contacts:
K1 to K5:

changeover contact (voltage-free)

K6:

normally open contact (voltage-free)

Fig. 64. XF524A and XF529 Digital Output module

NOTE: Maximum voltage for U.S. is 24 V.

NOTE: Both modules are fully pin compatible.

Beginning with V3.04.00 firmware, the online point attribute
normally open/normally closed (NO/NC) defines the relation
between the physical input signal and its logical status. See
Table 10.

Table 10. NO/NC attribute and output characteristic

Relay On/Off

NO/NC attribute

Logical status

On

NO

1

Off

NO

0

On

NC

0

Off

NC

1